Fan replacement procedure
Power off the Clean Power VFD.
Disconnect the control terminals block.
Check the remaining voltage on the DC bus.
Wait 5 minutes for the capacitor to discharge and check that the remaining voltage is lower than 50 VDC.
Disconnect the power line inputs R/S/T (L1/L2/L3). Keep the protective ground connected.
Disconnect the motor from the output terminals U/V/W.
Disconnect the grounding.
Unscrew the upper screws that maintain the Clean Power VFD on its panel.