Table C.11 Maximum Number of Conductors in Rigid PVC Conduit, Schedule 40 and HDPE Conduit

(Based on Chapter 9: Table 1, Table 4, and Table 5)

Type Conductor Size
(AWG/kcmil)
Trade Size (in)
1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4
THHN,
THWN,
THWN-2
14 11 21 34 60 82 135 193 299 401 517
12 8 15 25 43 59 99 141 218 293 377
10 5 9 15 27 37 62 89 137 184 238
8 3 5 9 16 21 36 51 79 106 137
6 1 4 6 11 15 26 37 57 77 99
4 1 2 4 7 9 16 22 35 47 61
3 1 1 3 6 8 13 19 30 40 51
2 1 1 3 5 7 11 16 25 33 43
1 1 1 1 3 5 8 12 18 25 32
1/0 1 1 1 3 4 7 10 15 21 27
2/0 0 1 1 2 3 6 8 13 17 22
3/0 0 1 1 1 3 5 7 11 14 18
4/0 0 1 1 1 2 4 6 9 12 15
250 0 0 1 1 1 3 4 7 10 12
300 0 0 1 1 1 3 4 6 8 11
350 0 0 1 1 1 2 3 5 7 9
400 0 0 0 1 1 1 3 5 6 8
500 0 0 0 1 1 1 2 4 5 7
600 0 0 0 1 1 1 1 3 4 5
700 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 1 1 1 2 3 4
800 0 0 0 0 1 1 1 2 3 4
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 1 1 1 3 3