Table 450.3(B) Maximum Rating or Setting of Overcurrent Protection for Transformers 1000V and Less (as Percentage of Transformer Rated Current)

Protection Method Primary Protection Secondary Protection (See Note 2)
Currents of 9 Amperes or More Currents Less Than 9 Amperes Currents Less Than 2 Amperes Currents of 9 Amperes or More Currents Less Than 9 Amperes
Primary only protection 125% (See Note 1) 167% 300% Not required Not required
Primary and secondary protection 250% (See Note 3) 250% (See Note 3) 250% (See Note 3) 125% (See Note 1) 167%