Table 310.16 Ampacities of Insulated Conductors with Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried)

Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, for Conductors rated 60°C through 90°C (140°F through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size AWG or kcmil Temperature Rating of Conductor (See Table 310.4(A)) Area (circular mills)
60°C (140°F) 75°C (167°F) 90°C (194°F) 60°C (140°F) 75°C (167°F) 90°C (194°F)
Types TW, UF Types RHW, THHW, THW, THWN, XHHW, XHWN, USE, ZW Types TBS, SA, SIS, FEP, FEPB, MI, PFA, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, XHWN, XHWN-2, XHHN, Z, ZW-2 Types TW, UF Types RHW, THHW, THW, THWN, XHHW, XHWN, USE Types TBS, SA, SIS, THHN, THHW, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, XHWN, XHWN-2, XHHN
COPPER ALUMINUM OR COPPER-CLAD ALUMINUM
14 15 20 25 - - - 4,110
12 20 25 30 15 20 25 6,530
10 30 35 40 25 30 35 10,380
8 40 50 55 35 40 45 16,510
6 55 65 75 40 50 55 26,240
4 70 85 95 55 65 75 41,740
3 85 100 115 65 75 85 52,620
2 95 115 130 75 90 100 66,360
1 110 130 145 85 100 115 83,690
1/0 125 150 170 100 120 135 105,600
2/0 145 175 195 115 135 150 133,100
3/0 165 200 225 130 155 175 167,800
4/0 195 230 260 150 180 205 211,600
250 215 255 290 170 205 230 -
300 240 285 320 195 230 260 -
350 260 310 350 210 250 280 -
400 280 335 380 225 270 305 -
500 320 380 430 260 310 350 -
600 350 420 475 285 340 385 -
700 385 460 520 315 375 425 -
750 400 475 535 320 385 435 -