Table 310.12 Single-Phase Dwelling Services and Feeders
Service or Feeder Rating
(Amperes)
Conductor Size
(AWG/kcmil)
Copper
Aluminum or Copper-Clad Aluminum
100
4
2
110
3
1
125
2
1/0
150
1
2/0
175
1/0
3/0
200
2/0
4/0
225
3/0
250
250
4/0
300
300
250
350
350
350
500
400
400
600