STO acceptance test
Procedure
Stop the Clean Power VFD if its is running.
Give a stop command
Switch off the power input line
Isolate the Clean Power VFD from the main line by a disconnector.
Motor is stopped and the motor system is safely disconnected from power.
Wait 5 minutes for the Clean Power VFD capacitors to be discharged.
Check that the STO circuit is correctly wired against the wiring diagram.
Check that proper cables are used and terminals are tighten with the recommended torque.
When previous steps have been checked and pass the verification, then switch on the disconnector to power up the Clean Power VFD.
Open the STO circuit.
Give a start command to verify that the STO function blocks the Clean Power VFD's operation.
The drive displays a warning. The motor should not start.
Reset and restart.
Close the STO circuit.
Reset the Clean Power VFD status.
Give a start command.
Check that the motor runs normally.
Test during running.
While the motor is running normally,
open one of the STO inputs.
The motor should stop
Give a start command. The motor must remain standstill.
Reset and restart.
Close the STO circuit.
Reset the Clean Power VFD status.
Give a start command.
The motor runs.
Test STO channel lost.
Open one of the STO inputs.
The motor stops and the alarm of lost STO channel is raised
Reset and restart
Close the STO input.
Reset the Clean Power VFD status.
Give a start command.
The motor runs normally.
Test STO second channel lost.
Open the other STO input.
The motor stops and the alarm of lost STO channel is raised
Reset and restart.
Close the STO input
Reset the Clean Power VFD status.
Give a start command.
The motor runs normally.