Power Output
Output current capability⚓
SDB1-2-185 ratings | ||
|---|---|---|
Rated output current | Normal operation (continuously available without overload) | 33 A |
Heavy duty operation | 24 A | |
Maximum Transient Output current | Normal operation | 110% during 60s every 10 min at 40 °C (104 °F) |
Heavy duty operation | 150% during 60s every 10 min at 40 °C (104 °F) 130% during 60s every 10 min at 40 °C (104 °F) 125% during 60s every 10 min at 40 °C (104 °F) | |
Permissible temporary current boost (motor starting) | 1.8 x In during 2 s |
Motor power⚓
Motor power values are indicative. They vary with the motor type, technology and manufacturer.
The Clean Power VFD must not be selected from motor power rating.
The Clean Power VFD must be selected by skilled and experienced personnel.
The Clean Power VFD must be selecting according to motor FLA, the load's driving force and the movement cycle, and the operating environment.
Duty cycles | SDB-1-2-185 | ||
|---|---|---|---|
Motor Power | Normal duty | 3 x 380 .. 460 VAC , 50/60Hz | 18.5 kW / 25 HP |
Heavy duty | 15 kW / 20 HP |
Frequencies⚓
Output Frequency range of the drive | 0.001 to 0.5 kHz |
Speed drive output Frequency | 0.1 to 120 Hz |
Nominal switching frequency | 105 kHz |
Effective switching frequency | 210 kHz |