Deratings
Current ratings of the Clean Power VFD must be derated according to the environment conditions.
Ambient temperature derating⚓
Temperature range | SDB-1-2-185 |
40 °C | UL tested value |
-15...50 °C | without derating |
50...60 °C | Derate 2% for every 1 °C (1.8 °F) |
Altitude derating⚓
In altitude up to 2000 m (6600 ft) above sea level, there isn't any derating to apply to the maximum output current.
For use in altitude over 2000 m (6600 ft) above sea level, please contact SmartD Technologies Inc.