Control I/Os

Clean Power VFD auxiliary power input

The Smart Drive is equipped with auxiliary DC power input.

While this input is powered properly, the control functions of the Clean Power VFD operate even if the main power line is disconnected.

Voltage

24 VDC

Limits

20.4 VDC to 28.8 VDC

Digital inputs

Digital inputs follow IEC 61131-2 type 1

Quantity

4 digital inputs. Programmable

Input logic

Wire-able as sink or source, configurable by software.

Default: source

Voltage levels in source mode

ON

18 .. 24 V

Off

0 .. 5V

Voltage levels in sink mode

ON

0 .. 5V

OFF

18 .. 24 V

Current consumption

6 mA

Output power for digital inputs

+24VDC (20% .. +20%) / 200 mA

Safe torque off (STO) inputs

Safe torque off (STO) inputs follow IEC 61131-2 type 1

Quantity

2

SIL capacity level

conformed to IEC61800-5-2

SIL 3

Stop category

Category 0

STO input reaction time

20 ms

STO input filtering time

5 ms

Nominal voltage of STO enabling input

24 V

Maximum input voltage

28.8 V

Logic threshold

10V (+/- 5V)

Low state maximum voltage for disable to SIL3

5 V

Analog inputs

Quantity

3 analog inputs. Programmable

Input types

0..10VDC

0..20mA / 4..20mA

0..24VDC

Impedance to read PTC temperature sensor

Default: 0..10VDC

Input impedances

0..10VDC

0..20mA / 4..20mA

0..24VDC

> 2.7 k Ohms

165 Ohms

25 k Ohms

Resolution

12 bits

Time response

7 ms

Accuracy

± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F)

Reference analog input power supply

+10 VDC / tolerance ± 2% for the temperature range of 20 °C to 30 °C / Current : maximum 10 mA, short circuit protected.

Digital outputs

Quantity

3

Type

relay

Relay 1

contact arrangement

SPDT (form C)

NO contact features

Resistive load, AC: 5 A @ 250 V / DC 5 A @ 30 V

NC contact features

Resistive load, AC: 3 A @ 250 V / DC 3 A @ 30 V

Relay 2

contact arrangement

SPST, NO (form A)

NO contact features

Resistive load, AC: 3 A @ 250 V / DC 3 A @ 30 V

Relay 3

contact arrangement

SPST, NO (form A)

NO contact features

Resistive load, AC: 3 A @ 250 V / DC 3 A @ 30 V

Analog outputs

Quantity

2 analog outputs. Programmable

Output types

0..10VDC ( 20 mA max.)

0..20mA / 4..20mA

Output impedances

0..10VDC

0..20mA / 4..20mA

500 ohms minimum

75 ohms maximum

Resolution

12 bits

Response time

50 ms (worst case from 0 to max output)

Accuracy

± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F)