Alarms and troubleshooting suggestions
When an alarm occurs, refer to the following table for possible causes and suggested remedies.
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
DC Over voltage | Deceleration time is too short compared to load inertia. | Increase deceleration time |
The input voltage is too high. | Check if the input voltage is above the Clean Power VFD specifications. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
DC Under Voltage | The input voltage is too low. | Check if the input voltage is below the Clean Power VFD specifications. |
If there's a contactor upstream of the Clean Power VFD, it may be defective. | Check operation and connection of the upstream contactor. If defective, replace it. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Drive over temperature | There is a problem with the Clean Power VFD cooling. | Check if a foreign object is obstructing the air inlet or outlet. |
The cooling fan is defective. | Replace the fan. | |
The ambient temperature is too high. | Keep the ambient temperature below the specified max. operating temperature of the Clean Power VFD. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Faulty cooling fan | A foreign object is obstructing the fan's air vent. | Remove the foreign object from the air inlet or outlet. |
The cooling fan needs to be replaced. | Replace the fan. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Motor Over current | Short-circuit detected on motor. | Check if there is any short circuits and grounding between the U, V, W and motor. |
Acceleration/deceleration time is too short compared to load inertia. | Increase acceleration/deceleration time. | |
The Clean Power VFD load (motor + mechanical load) is greater than the Clean Power VFD capacity. | Replace the Clean Power VFD by a model that fits the connected load. | |
Torque compensation is too large. | Reduce torque compensation. | |
The motor insulation is damaged. | Replace the motor. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Application overload. | The load is greater than the motor capacity. | Replace both motor and Clean Power VFD to fit the application load constraints. |
The set value for overload alarm is too low. | Increase the set value for overload alarm. | |
The torque boost value is too high. | Decrease the torque boost value. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Motor current unbalanced | Increase of current to at least one winding raising that winding temperature. | Potential single phase load connected on one of the Clean Power VFD output.Check and fix the wiring |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Motor phase loss | The output wiring is faulty. | Check output wiring on Clean Power VFD side and motor side. |
If you use a contactor between the Clean Power VFD and the motor, it may be defective. | Check the contactor wiring.Replace the contactor. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Motor overtemperature | The motor has overheated. | Reduce the load or operating frequency. |
The PTC sensor's wiring is defective. | Check the wiring of the PTC sensors. | |
The PTC sensors are defective. | Disconnect the sensors from the Clean Power VFD check their resistance. If defective, replace them. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Motor ground fault | A ground fault has occurred on the output wiring. | Check output wiring on the Clean Power VFD side and motor side. |
The motor insulation is damaged. | Replace the motor. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Power input Line overcurrent | The Clean Power VFD has been protected from overload and resulting overheating. | Check that the motor with its load do not exceed the overcurrent and duration limits as specified. Change the Clean Power VFD for a higher capacity Clean Power VFD. |
Alarm | Possible Cause | Suggested remedy |
|---|---|---|
Power input Line phase loss | The input wiring is faulty. | Check input wiring. |
If there's a contactor upstream of the Clean Power VFD, it may be defective. | Check operation and connection of the upstream contactor. If defective, replace it. |