| Description | Load, A | Load, VA | Circuit Breaker, A | Poles | Volts | Code | Load Classiffication | Notes |
|---|---|---|---|---|---|---|---|---|
| Appliances | ||||||||
| Coffee Maker | 12.5 | 1,500 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Dishwasher | 10 | 1,200 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI Breaker |
| Dishwasher and Garbage Disposal Combination (DW/GD) | 12.5 | 1,500 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI Breaker. Typical application |
| Dryer | 24 | 5,000 | 30 | 2 | 208 or 240 | 6 | Other | GFCI Breaker. Typical receptacle mounting height 3'10" |
| Electric Range | 38.5 | 8,000 | 50 | 2 | 208 or 240 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8. Typical receptacle mounting height is 4", located behind the range on the left or on center when facing the appliance |
| Garbage Disposal | 6.3-6.9 | 800-850 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI Breaker |
| Hood | 2.5 | 300 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Ice Maker | 12 | 1440 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI Breaker |
| Microwave (MW) | 12.5 | 1,500 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Refrigerator | 7.5 | 900 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Toaster | 12.5 | 1,500 | 20 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Undercounter Refrigerator | 1 | 120 | 15 | 1 | 120 | 5 | Kitchen Equipment | GFCI per NEC Article 210.8 |
| Vending Machine | 12.5 | 1,500 | 20 | 1 | 120 | 6 | Other | GFCI Breaker |
| Washing Machine | 12.5 | 1,500 | 20 | 1 | 120 | 6 | Other | GFCI Breaker. Typical receptacle mounting height 3'10" |
| Other Loads | ||||||||
| Description | Load, A | Load, VA | Circuit Breaker, A | Poles | Volts | Code | Load Classiffication | Notes |
| Car Charger | 30 | 6,240 | 40 | 2 | 208 | 1 | Continuous | |
| Copier | 12.5 | 1,500 | 20 | 1 | 120 | 6 | Other | |
| EPO or Shunt Trip Circuits | - | 100 | 20 | 1 | 120 | 6 | Other | Typically for boiler/gas water heaters, and elevator shunt trip circuit |
| Fire Alarm Control Panel (FACP) | 5 | 600 | 20 | 1 | 120 | 6 | Other | |
| Illuminated Sign | 10 | 1,200 | 20 | 1 | 120 | 1 | Lighting | Provide controls |
| Printer | - | 800 | 20 | 1 | 120 | 6 | Other | |
| Projection Screen | - | 300 | 20 | 1 | 120 | 6 | Other | |
| Projector | - | 1,500 | 20 | 1 | 120 | 6 | Other | |
| Snowmelt (gutter, downspout) | - | - | - | - | - | 4 | Electrical Heating | GFPE Breaker. Typically, 30 watts per linear foot |
| Snowmelt (surface) | - | - | - | - | - | 4 | Electrical Heating | GFPE Breaker. Typically, 50 watts per square foot |
| Trash Chute | - | 600 | 20 | 1 | 120 | 6 | Other | |
| Trash Compactor (Commercial) | 16.7 | 6,016 | 30 | 3 | 208 | 3 | Motor | 5 hp. Provide dedicated 20A 120V circuit (1,500VA) for controls. |
| Treadmill | - | 1,800 | 20 | 1 | 120 | 6 | Other | |
| Mechanical Loads | ||||||||
| Description | Load, A | Load, VA | Circuit Breaker, A | Poles | Volts | Code | Load Classiffication | Notes |
| Air Conditioner Unit (AC) | - | - | - | - | - | 8 | Cooling HVAC | Typically, interior unit, powered from exterior CU or ACCU unit. Do not show electrical connection. Condensate pump is required. |
| Air Handling Unit (AHU) | - | - | - | - | - | 6 | Other | |
| Air Compressor | - | - | - | - | - | 3 | Motor | |
| Boiler (B) | 12.5 | 1,500 | 20 | 1 | 120 | 6 | Other | Boiler EPO Note is required |
| Condensing Unit (CU or ACCU) |
- | - | - | 2,3 | 208 | 8 | Cooling HVAC | Typically, single point of the power connection at CU/ACCU unit. Interior AC unit is powered from CU/ACCU unit. |
| Electric Cabinet Unit Heater (ECUH) | - | - | - | - | - | 7 | Heating HVAC | Integrated disconnect |
| Electric Duct Heater (EDH) | - | - | - | - | - | 7 | Heating HVAC | |
| Electric Unit Heater (EUH) | - | - | - | - | - | 7 | Heating HVAC | |
| Exhaust Fan (EF) | - | - | - | - | - | 3 | Motor | |
| Fire/Smoke Damper, Motorized Damper | - | 50 | 20 | 1 | 120 | 3 | Motor | |
| Make-Up Air Unit (MAU) | - | - | - | 3 | - | 6 | Other | |
| Packaged Terminal Air Conditioner (PTAC) | - | - | - | - | - | 6 | Other | |
| Rooftop Unit (RTU) | - | - | - | - | - | 6 | Other | |
| Transfer Fan (TF) | - | - | - | - | - | 3 | Motor | |
| Plumbing Loads | ||||||||
| Description | Load, A | Load, VA | Circuit Breaker, A | Poles | Volts | Code | Load Classiffication | Notes |
| Domestic Water Booster Pump (DWBP) | - | - | - | 3 | - | 3 | Motor | Integrated disconnect |
| Electric Heat Trace | - | - | - | - | - | 4 | Electrical Heating | GFPE Breaker. Typically, 8-12 watts per linear foot |
| Electric Water Cooler (EWC) | 5 | 600 | 20 | 1 | 120 | 6 | Other | GFCI Breaker. Drinking fountain or bottle filler. One receptacle per location |
| Electric Water Heater (EWH) | - | - | - | - | - | 4 | Electrical Heating | For 120V units in breaker room application, it is acceptable to have load code "5" and load classification "Kitchen Equipment" |
| Elevator Sump Pump (ESP) | - | - | - | - | - | 3 | Motor | |
| Sump Pump (SP) | - | - | - | - | - | 3 | Motor | |