NetBotz Humidity Check
The NetBotz Humidity Check monitors the humidity reading and sensor status of the specified temperature sensor.
Basic Check information
Check Type | SNMP |
Instances on a Device | 68 |
Supported Systems/Applications | Any NetBotz device that has an attached humidity sensor. |
Troubleshooting
Issue | Corrective Action |
---|---|
Failed | Please check that the correct SNMP community string is configured in Network Discovery for the device |
201 Exception OID_TYPE_NOSUCHOBJECT | Missing OID object on the device for specific metric |
OID/Calculation
Metric Name | OID/Calculation | Description |
---|---|---|
Humidity | 1.3.6.1.4.1.5528.100.4.1.2.1.8 | The humidity reading reported by the sensor. |
Sensor Status | 1.3.6.1.4.1.5528.100.4.1.2.1.3 | An integer value representing whether or not the humidity sensor is connected or disconnected. The Check transitions to a Failed state if the door switch reports a disconnected status. |
Sensor Status Description | 1.3.6.1.4.1.5528.100.4.1.2.1.3 | A description of the sensor’s status. |