NetBotz Door Switch Check
The NetBotz Door Switch Check monitors whether or not the door switch is open or closed, and the status of the door sensor.
Basic Check information
| Check Type | SNMP |
| Instances on a Device | 68 |
| Supported Systems/Applications | Any NetBotz device that has an attached door switch. |
| Device Class | Other |
Troubleshooting
| Issue | Corrective Action |
|---|---|
| Failed | Please check that the correct SNMP community string is configured in Network Discovery for the device |
| 201 Exception OID_TYPE_NOSUCHOBJECT | Missing OID object on the device for specific metric |
OID/Calculation
| Metric Name | OID/Calculation | Description |
|---|---|---|
| Door Switch Status | 1.3.6.1.4.1.5528.100.4.2.2.1.2 | An integer value representing whether or not the door switch is connected - the door is closed - or disconnected - the door is open. The Check transitions to a Failed state if the door switch reports a disconnected status. |
| Door Switch Status Description | 1.3.6.1.4.1.5528.100.4.2.2.1.2 |
Reports either Connected or Disconnected. |
| Sensor Status | 1.3.6.1.4.1.5528.100.4.2.2.1.3 |
The health status of the sensor:
This status is mapped as:
|
| Sensor Status Description | 1.3.6.1.4.1.5528.100.4.2.2.1.3 | A description of the health status of the sensor. |